Power Quality — Surge Protection

Protecting Critical Production Lines from Voltage Transient Damage

Automotive battery manufacturing facility, Pune — persistent PLC and VFD failures traced to severe transient disturbances generated by continuous switching of industrial loads across the distribution system.

Industry

Battery Manufacturing

Location

Pune, India

Service

PQ Audit + TVSS

Year

2024

1 The Challenge

Repeated equipment failures with no clear cause

Persistent PLC and VFD malfunctions, frequent electronic card failures, and nuisance tripping across production lines — with no apparent cause from standard maintenance checks.

275 transient events in 30 minutes at main production panel — up to 457V magnitude
158 events in 60 min on production line — neutral-to-ground voltage reaching 11–12V
56 events in 40 min on another line — high oscillatory and impulse transients
101 events in 53 min — automation systems under continuous stress
Root cause: continuous switching of industrial loads generating repetitive transients across the distribution system
2 The Action

Measure first — then solve

Pre-installation Power Quality Audit using a Class A analyser — capturing transient events, magnitudes, and neutral-to-ground voltage across all critical panels before recommending any solution.

Site measurement at all critical production panels — transient capture at 200kS/sec
Root cause analysis — identified transient sources and propagation paths
TVSS installed at main incomer (L-L-L-G) and sensitive load incomers (L-N-G)
Dedicated surge protection at each VFD, PLC, and SMPS section
Post-installation audit conducted 3 months later to verify performance through data
3 The Results

Verified by post-installation measurement

93%
Reduction in transient events
0.72V
Neutral-to-ground voltage achieved
Transient events (30 min) 275 20
Transient magnitude Up to 457V Very small
Voltage profile Unstable Stable
N-G voltage Elevated 0.72V
4 The Benefits

Impact across three dimensions

Technical — Drastic reduction in transient magnitude and frequency, improved voltage stability, safe neutral-to-ground voltage levels
Operational — Reduced PLC and VFD malfunction incidents, reduced unplanned production downtime, improved process continuity
Maintenance — Fewer electronic card failures, lower frequency of maintenance interventions, reduced risk of unexpected shutdowns
Long-term — Extended service life of sensitive automation equipment and reduced total cost of ownership

Facing similar challenges at your facility?

Talk to our engineers — we will assess your electrical system and recommend the right solution.

Discuss your requirements Our audit services

More case studies being added across EMS, Harmonic Mitigation, LV Panels, and ISO 50001 engagements.

Energy Management Systems Harmonic Mitigation Power Quality Audit LV Panels ISO 50001